產品(pin)詳(xiang)情 Product details
概述(shu)
XGN2-12箱型(xing)固定(ding)式金屬封閉開關(guan)設(she)(簡稱“開關(guan)設(she)備”),適用(yong)于額定(ding)電(dian)(dian)壓為3.6~12KV、50Hz,額定(ding)電(dian)(dian)流630A~3150A三相交流單母(mu)(mu)線、雙母(mu)(mu)線、單母(mu)(mu)線帶旁路系統,作為接(jie)受和分(fen)配電(dian)(dian)能之用(yong)。可滿足各種類(lei)型(xing)發電(dian)(dian)廠、變電(dian)(dian)站(zhan)(所)及工礦企業(ye)使用(yong)要(yao)求。
本(ben)產品符(fu)含國家標準GB3906(3~35KV交流金(jin)屬封閉開關設(she)備(bei)》,lEC60298《交流金(jin)屬封閉開關設(she)備(bei)和(he)控制(zhi)設(she)備(bei)》、及DL/T402、DL/T404標準,達(da)到“五(wu)防(fang)”閉鎖要(yao)求(qiu)。
型號及含義
正常使(shi)用條件
◆周圍空氣溫(wen)度(du):-15℃~+40℃;
◆海拔高度:1000m及(ji)以下;
◆濕度(du):日平(ping)(ping)均(jun)值不大于(yu)95%,水(shui)蒸(zheng)氣壓(ya)力日平(ping)(ping)均(jun)值不超22KPA月(yue)平(ping)(ping)均(jun)值不大于(yu)90%,水(shui)蒸(zheng)氣壓(ya)力月(yue)平(ping)(ping)均(jun)值不超1.8KPA;
◆地震強度:不超過8級;
◆沒有腐蝕性(xing)或可燃性(xing)氣體等明(ming)顯污染的(de)場所。
注:有特(te)殊要(yao)求(qiu)可與本公司協商(shang)解決。
主要(yao)技術參數
主(zhu)電路(lu)組合方案示例
結構特點(dian)
1.XGN2-12(Z)開(kai)關(guan)柜為金屬封閉箱式結構,柜體骨架(jia)由角鋼焊接(jie)而成,柜內分(fen)為斷(duan)路器(qi)室(shi)、母線室(shi)、電(dian)纜室(shi)儀表(biao)室(shi)等,室(shi)與室(shi)之(zhi)間用鋼板(ban)隔開(kai)。
2.斷(duan)路(lu)器(qi)(qi)室在(zai)柜體前下部,斷(duan)路(lu)器(qi)(qi)的轉動(dong)由拉桿與(yu)操動(dong)機構連(lian)接(jie)(jie)(jie),斷(duan)路(lu)器(qi)(qi)上接(jie)(jie)(jie)線(xian)端子(zi)與(yu)上隔(ge)離(li)開關連(lian)接(jie)(jie)(jie),斷(duan)路(lu)器(qi)(qi)下接(jie)(jie)(jie)線(xian)端子(zi)與(yu)電(dian)流互(hu)感器(qi)(qi)連(lian)接(jie)(jie)(jie),電(dian)流互(hu)感器(qi)(qi)與(yu)下隔(ge)離(li)開關的接(jie)(jie)(jie)線(xian)端子(zi)連(lian)接(jie)(jie)(jie),斷(duan)路(lu)室還設(she)有壓力釋放通道(dao),若內部電(dian)弧(hu)發生時,氣體可通過排氣通道(dao)將壓力釋放。控(kong)制(zhi)設(she)備、及DLT402、DL/T404標準(zhun),達到(dao)“五防”閉鎖要求。
3.母(mu)線(xian)室在柜休后(hou)上部(bu),為(wei)了減(jian)小(xiao)柜體離(li)(li)度,母(mu)線(xian)呈品字形(xing)排列,以7350N抗(kang)彎強度的瓷質絕緣子(zi)支持,母(mu)線(xian)與上隔(ge)(ge)離(li)(li)開關接(jie)線(xian)端子(zi)相連接(jie),相鄰兩柜母(mu)線(xian)室之間可隔(ge)(ge)離(li)(li)。
4.電(dian)(dian)(dian)纜(lan)室(shi)在柜體下(xia)部的(de)后(hou)方,電(dian)(dian)(dian)纜(lan)室(shi)內(nei)支(zhi)持絕緣子可(ke)設有電(dian)(dian)(dian)壓監視裝置,電(dian)(dian)(dian)纜(lan)固定(ding)在支(zhi)架(jia)上,對(dui)于主(zhu)結線(xian)為聯絡方案時(shi),本室(shi)則為聯絡電(dian)(dian)(dian)纜(lan)室(shi)。繼(ji)電(dian)(dian)(dian)器室(shi)在柜體上部前(qian)方,室(shi)內(nei)安(an)裝板(ban)可(ke)安(an)裝各種繼(ji)電(dian)(dian)(dian)器等,室(shi)內(nei)有端子排(pai)支(zhi)架(jia),門上可(ke)安(an)裝指(zhi)示儀(yi)表、信(xin)號(hao)元(yuan)件等二次(ci)元(yuan)件,頂部還可(ke)布置二次(ci)小母線(xian)。
5.斷(duan)(duan)路(lu)器(qi)的操(cao)動(dong)(dong)機(ji)(ji)構裝在(zai)正面(mian)左邊(bian)位置,其(qi)上(shang)方(fang)為(wei)隔離開關(guan)的操(cao)作及(ji)聯鎖機(ji)(ji)構。開關(guan)柜為(wei)雙(shuang)面(mian)維(wei)護(hu),前面(mian)檢(jian)修(xiu)繼電器(qi)室(shi)的二次(ci)元件,維(wei)護(hu)操(cao)動(dong)(dong)機(ji)(ji)構,機(ji)(ji)械聯鎖及(ji)傳動(dong)(dong)部分,檢(jian)修(xiu)斷(duan)(duan)路(lu)器(qi)。后面(mian)維(wei)修(xiu)主母線和電纜終(zhong)端,在(zai)斷(duan)(duan)路(lu)器(qi)室(shi)裝有照明燈(deng)。前門的下(xia)方(fang)設有與柜寬方(fang)向平(ping)行的接地銅(tong)母線,其(qi)截面(mian)為(wei):3×30mm。
6.機械聯(lian)(lian)鎖:為了防(fang)止(zhi)(zhi)帶(dai)負荷分合(he)(he)隔離開關(guan),防(fang)止(zhi)(zhi)誤分誤合(he)(he)斷(duan)路器,防(fang)止(zhi)(zhi)誤入帶(dai)電間隔;防(fang)止(zhi)(zhi)帶(dai)電合(he)(he)接(jie)地開關(guan);防(fang)止(zhi)(zhi)接(jie)地刀合(he)(he)閘位置誤合(he)(he)斷(duan)路器,開關(guan)柜設有(you)相 應(ying)可靠的機械聯(lian)(lian)鎖,保證操作(zuo)安全。產品外形尺寸(cun)及結(jie)構(gou)圖(tu)(見圖(tu)一、圖(tu)二、圖(tu)三)

外形、安裝尺寸及基礎示意圖
訂(ding)貨(huo)須(xu)知(zhi)
訂貨時須提供以下資料:
1.一(yi)次系統圖(tu)、平面布置圖(tu);
2.輔助電路電氣原理圖,端子排列圖;
3.開關設備電器元件的(de)型(xing)號、規(gui)格(ge)、數量;
4.主(zhu)母(mu)線(xian)、分支(zhi)母(mu)線(xian)的規格、材質;
5.備品、備件(jian)的(de)名稱(cheng)及數量;
6.特殊(shu)要求(qiu)同我公司協商。